Distributed control system NL-Ex series with intrinsically safe circuits (i) for automation of technological processes on explosive industrial objects

The control system below includes input-output modules with intrinsically safe circuits and can be used in conjunction with PLC NLcon-1AT-Ex or any computer or PLC (e.g. NLcon-CE), if they located in the safe area and connected to the intrinsically safe parts trough safety barrier or interface converter NL-232C-Ex. A series of NL-Ex has certificate of conformity to industrial safety requirements in accordance with Russian GOST R 51330.0-99, 51330.10-99 GOST, GOST R 51330.20-99.

The modules below are software compatible with similar module of ADAM, ICP and use standard Modbus RTU or DCON protocols.

I/O modules NL-Ex series, intrinsic safety i

Picture (Click to view better )

Features

Price, USD

In Stock


NL
con-1AT-Ex
User Manual
(250 К)

Ex-Attachment (0,7 M)

    PLC
  • ExiaIICT6 or ExiaIIBT6
  • C-programmed
  • RS-232 port for program  loading
  • FLASH 128 kb program memory
  • ATMEGA 128 (RISC 8 bit) 16 MIPS processor
  • real time clock
  • RS-485 port for Modbus RTU or DCON fieldbus

250

In Stock


NL-8TI-Ex
User Manual
(1,2 M)

Ex-Attachment (0,7 M)

    Termocouple Analog Input Module
  • ExiaIICT6 or ExiaIIBT6
  • 8 differential input channel for termocouple K, J, B, L, E, S, R, N, T or voltage. Programmable controlled range ±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2,5 V or current ±20 mA
  • 16 bit resolution
  • hardware diagnostic of sensor disconnects
  • galvanic decoupling 2500 V
  • relative error ±0,05%
  • common mode regection ratio (CMRR) for 50 Hz noise is 100 dB
  • temperature range -40 ... +70 °С
  • RS-485 interface
  • independent range or termocouple type set for each channel (for DCON protocol only)
  • default protocol is DCON (ADAM-compatible) and MODBUS RTU can be set programmatically
  • PID or relay regulator

300

In Stock


NL-4RTD-Ex
User Manual
(1,2 M)

Ex-Attachment (0,7 M)

    RTD Input Module
  • ExiaIICT6 or ExiaIIBT6
  • for temperature measurement ans control using cuprum, platinum and nickel RTD sensors
  • 4 differential RTD input channel
  • independent range or RTD type set for each channel (for DCON protocol only)
  • 4 RTDs using 4-wire connection or 3 RTDs using 3-wire connection
  • 16 bits
  • hardware diagnostic of sensor disconnects and shorts
  • galvanic decoupling 2500 V
  • 11 types of protection: от перенапряжения и токовой перегрузки по входу, выходу, интерфейсу, от перегрева, статического электричества и др.
  • relative error ±0,05%
  • common mode regection ratio (CMRR) for 50 Hz noise is 100 dBпомехи общего вида с частотой 50 Гц - не менее 100 дБ
  • temperature range from -40 to +70 °С
  • RS-485 interface
  • default protocol is DCON (ADAM-compatible) and MODBUS RTU can be set programmatically
  • 3 isolated discrete outputs
  • PID or relay regulator

 

317

In Stock


NL-8AI-Ex
User Manual
(1,2 M)

Ex-Attachment (0,7 M)

    Analog Input Module
  • ExiaIICT6 or ExiaIIBT6
  • for voltage and current input and discrete signal output
  • 16 single or 8 differential input channel
  • input range is set by software: ±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V, ±20 mA
  • independent range setting for each channel (for DCON protocol only)
  • 16 bits
  • galvanic inputs decoupling 2500 V
  • 11 types of protection
  • frequency range 13,1 Hz
  • measuring error is ±0,1%
  • common mode regection ratio (CMRR) for 50 Hz noise is 100 dBпомехи общего вида с частотой 50 Гц - не менее 100 дБ
  • temperature range from -40 to +70 °С
  • RS-485 interface
  • default protocol is DCON (ADAM-compatible) and MODBUS RTU can be set programmatically
  • PID or relay regulator

300

In Stock


NL-16DI-Ex
User Manual
(920 К)

Ex-Attachment (0,7 M)

    Discrete Input Module
  • ExiaIICT6 or ExiaIIBT6
  • 16 discrete output cahnnels with group galvanic decoupling
  • LED display
  • galvanic decoupling 2500 V
  • 11 types of protection
  • reduced input current (2 mA or less)
  • input "0" logical level is 2 V
  • input "1" logical level is from ±4 to ±30 V
  • temperature range from -40 to +70 °С
  • RS-485 interface
  • default protocol is DCON (ADAM-compatible) and MODBUS RTU can be set programmatically
  • 2 isolated disctere outputs

222

In Stock


NL-8R-Ex
User Manual
(920 К)

Ex-Attachment (0,7 M)

    Relay output Module
  • ExiaIICT6 or ExiaIIBT6
  • 8 relay 2 A @=30V or 0.25 A @~220 V
  • 4 normal open and 4 switching contacts relay
  • protection for RS-485 interface and power supply line
  • temperature range from -40 to +70 °C
  • RS-485 interface
  • default protocol is DCON (ADAM-compatible) and MODBUS RTU can be set programmatically
211

In Stock


NL-16DO-Ex
User Manual
(920 К)

Ex-Attachment (0,7 M)

    Discrete Output Module
  • ExiaIICT6 or ExiaIIBT6
  • 16 discrete outputs on smart switches for 35В, 0.75 А load
  • 11 types of protection
  • galvanic decoupling voltage is 3,7 kV
  • temperature range is from -40 to +70 °C
  • RS-485 interface
  • default protocol is DCON (ADAM-compatible) and MODBUS RTU can be set programmatically
  • 3 isolated discrete inputs

211

In Stock


NL-2С-Ex
User Manual
(920 К)

Ex-Attachment (0,7 M)

    Counter and Frequency Meter Module
  • ExiaIICT6 or ExiaIIBT6
  • 2 independent channels 32 bit each
  • input frequency: up to 200 kHz
  • galvanic isolation of counter inputs voltage is 3.7 kV
  • non-isolated discrete inputs with programmtically set logical threshold
  • embedded source sypply for "dry contacts"
  • adjustable digital filter
  • counter enable inputs
  • temperature range from -40 to +70 °С
  • RS-485 interface
  • default protocol is DCON (ADAM-compatible) and MODBUS RTU can be set programmatically
  • 4 isolated discrete inputs

250

In Stock


NL
-485C-Ex
User Manual
(875 К)

Ex-Attachment (0,7 M)

    RS-485 Repeater
  • ExiaIICT6 or ExiaIIBT6
  • galvanic decoupling voltage 2500 V  
  • temperature range from -40 to +50 °С

179

In Stock


NL
-232C-Ex
User Manual
(875 К)

Ex-Attachment (0,7 M)

    RS-232 - RS-485 Interface Converter
  • [Exia]IIC or [Exia]IIB
  • galvanic decoupling voltage 2500 V
  • temperature range from -40 to +50 °С

179

In Stock


NL
-12V-Ex
User Manual
(457 К)

Ex-Attachment (0,7 M)

    Power Supply with Intrinsic Safety i
  • [Exia]IIC/[Exia]IIB or [Exia]I
  • intrinsic safety i output circuits
  • output voltage 12...13 В
  • output current 0,5/1 А
  • input supply voltage 220 / 127 / 36 V
  • temperature range from -40 to +50 °С

308

In Stock


    All the modules NL-Ex series are available now in modification with screwless spring clamp terminals WAGO

 

 


©RLDA, 2013              

© Microsoft, Windows, and the Windows CE are registered trademarks of Microsoft Corporation in the United States and/or other countries

RLDA, 8 Berjevoy spoosk, Taganrog 347900, Russia
Ph.:
(8634) 47-70-40, 47-70-44, mobile +7 928-132-1161, E-mail: info@RLDA.ru